·Ratings from 100A to 300A @ 40-480 VAC
·1200 Volts transient overvoltage
·Removable IP 20 touch-safe cover
·LED input status indicator
·UL/CE approved, RoHS/EMC compliant.
·Strengthened current design for heavy industrial loads
·Designed in according with the requirements of IEC 62314
·Zero-crossing (resistive loads) or instantaneous (inductive loads) output
PRODUCT SELECTION
Control Voltage | 100A | 120A | 150A | 200A | 300A |
90-280 VAC | SAM40100A | SAM40120A | SAM40150A | SAM40200A | SAM40300A |
40-140 VAC | SAM40100B | SAM40120B | SAM40150B | SAM40200B | SAM40300B |
4-32 VDC | SAM40100D | SAM40120D | SAM40150D | SAM40200D | SAM40300D |
MODEL NAME DEFINITIONS
OUTPUT SPECIFICATIONS (1)
Description | 100A | 120A | 150A | 200A | 300A |
Operating Voltage (47-63Hz) [Vrms] | 40-480 | 40-480 | 40-480 | 40-480 | 40-480 |
Transient Overvoltage [Vpk] | 1200 | 1200 | 1200 | 1200 | 1200 |
Maximum Off-State Leakage Current @ Rated Voltage [mArms] | 8 | 8 | 8 | 8 | 8 |
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] | 500 | 500 | 500 | 500 | 500 |
Maximum Load Current(2) [Arms] | 100 | 120 | 150 | 200 | 300 |
Minimum Load Current [Arms] | 0.15 | 0.15 | 0.15 | 0.15 | 0.15 |
Maximum 1 Cycle Surge Current (50/60Hz) [Apk] | 1050/1100 | 1260/1320 | 1528/1600 | 2100/2200 | 3056/3200 |
Maximum On-State Voltage Drop @ Rated Current [Vrms] | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 |
Thermal Resistance Junction to Case (Rjc) [°C/W] | 0.43 | 0.42 | 0.40 | 0.39 | 0.36 |
Maximum 1/2 Cycle I²t for Fusing (50/60 Hz) [A² sec] | 3751/3410 | 4501/4092 | 5626/5115 | 7502/6820 | 10230/11253 |
Minimum Power Factor (with Maximum Load) | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
Weight (typical) [Gram] | 142 | 142 | 232 | 232 | 232 |
INPUT SPECIFICATIONS (1)
Description | SAM40xxA | SAM40xxB | SAM40xxD |
Control Voltage Range | 90-280 Vrms | 40-140 Vrms | 3-32 VDC |
Maximum Reverse Voltage | - | - | -32 |
Minimum Turn-On Voltage | 90 Vrms | 90 Vrms | 3.0 VDC |
Minimum Turn-Off Voltage | 10 Vrms | 10 Vrms | 1.0 VDC |
Minimum Input Current [mA] | 5 | 5 | 7 |
Maximum Input Current [mA] | 15 | 15 | 20 |
Nominal Input Impedance | Current Regulated | Current Regulated | Current Regulated |
Maximum Turn-On Time(3) [msec] | 20 | 20 | 1/2 cycle |
Maximum Turn-Off Time [msec] | 30 | 30 | 1/2 cycle |
GENERAL SPECIFICATIONS
Description | Parameters |
Dielectric Strength, Input/Output/Base (50/60Hz) | 4000 Vrms |
Minimum Insulation Resistance (@ 500 V DC) | 109 Ohm |
Maximum Capacitance, Input/Output | 8 pF |
Ambient Operating Temperature Range | -40 to 80°C |
Ambient Storage Temperature Range | -40 to 125 °C |
Housing Material | UL E211125: 94 V-0 |
Terminal Material | Gilded |
Baseplate Material | Copper |
Humidity | 85% non-condensing |
LED Input Status Indicator | Red |
RECOMMENDED MODEL & HEATSINK
Choosing compatible current is critical in selecting a right model of solid state relay. Our engineers recommend SSR models according to actual applications and internal components of relay. For example, when solid state relay is used for electric heating, because of the cold resistance effect (the resistance value is 60% of heating wire value when it is in cold state), the SSR’s current should be 1.67 times bigger than actual working current in order to prevent the over-current of solid state relay. The recommendations for the other types of application are provided in the similar reasons. Heatsink in the table are compatible (size and thermal parameters) with the corresponding SSRs.
Application to Electric Heating
Continuous Load Current | 0.1A-60A | 0.15A-110A | 0.3A-190A | |
Recommended Model(4) | SAM40100D | SAM40150D | SAM40300D | |
Recommended Heatsink | Panel | T110 | T180 | Z170 |
Din Rail | CH120 |
Application to Single-Phase Motors
Continuous Load Current | 0.1A-20A | 0.15A-33A | 0.3A-53A | |
Recommended Model(4) | SAM40100D-R | SAM40150D-R | SAM40300D-R | |
Recommended Heatsink | Panel | G120 | G120 | T130 |
Din Rail | CH120 | CH120 |
Application to Three-Phase Motors (5)
Continuous Load Current | 0.1A-15A | 0.15A-25A | 0.3A-40A |
Recommended Model(4) | SAM40100D-R | SAM40150D-R | SAM40300D-R |
Recommended Panel Mount Heatsink(5) | T150 | T150 | T230 |
Application to Transformer Loads
Continuous Load Current | 0.1A-30A | 0.15A-50A | 0.3A-80A | |
Recommended Model(4) | SAM40100D-R | SAM40150D-R | SAM40300D-R | |
Recommended Heatsink | Panel | G120 | T130 | Z100 |
Din Rail | CH120 |
Application to Solenoid Valves
Continuous Load Current |
| 0.1A-10.9A | 0.15A-18.1A | 0.3A-29A |
Recommended Model(4) |
| SAM40100D-R | SAM40150D-R | SAM40300D-R |
Recommended Heatsink | Panel | G120 | G120 | G120 |
Din Rail | CH120 | CH120 | CH120 |
GENERAL NOTES
All parameters at 25°C and per section unless otherwise specified.
Heat sinking required, for derating curves see next page.
Turn-on time for random turn-on (-R) version is 0.1 msec.
It is DC control as a default in the recommendation table, but it can be changed to AC control according to demand.
Each Heatsink is suitable to assemble three solid state relays.
Copyright © 2022 Jiangsu GOLD Electric Control Technology Co., Ltd. - www.goldssr.com All Rights Reserved.